SADDLE TURBINE SERIES FLOWMETERS

Dec. 7, 2007
Turbine meters that provides a turbine meter insertion design for liquids that can be installed in small metal, composite or plastic piping. This meter is suitable for 2”, 3”, & 4” line sizes and is interchangeable amongst these sizes. The Saddle Turbine Series provides an economical insertion style meter for smaller pipe diameters and addresses applications in the HVAC market, physical industry, as well as hot and cold water applications. This series covers flow ranges from 25 GPM to 1650 GPM and provides linearity of +/-2% of reading or better. • Linear Flow Range: Extended Flow Range: • 2” schedule 40 pipe & 80 pipe 25 GPM TO 275 GPM 20 GPM TO 300 GPM • 3” schedule 40 pipe & 80 pipe 58 GPM TO 650 GPM 54 GPM TO 825 GPM • 4” schedule 40 pipe & 80 pipe 150 GPM TO 1650 GPM • No extended range • REPEATABILITY: ±.25% OUPUT SIGNAL: Output level - 10 mV RMS. • minimum. • BEARING TYPE: Hard Carbon Composite Sleeve • Bearings. • MAGNETIC COIL: Wave shape - sinusoidal. • DC resistance of sense coil - • 2000 OHMS. • Coil - magnetic pickup type. M-L • 3/8X1.52 with flying leads. • MATERIALS: Housing insert and rotor support are 316 • stainless steel. Rotor - 17.4 stainless • steel (standard). Saddle is PVC. • MAX TEMPERATURE: 140 DEG. F